Liebert Series 600T Instrukcja Użytkownika

Przeglądaj online lub pobierz Instrukcja Użytkownika dla Narzędzia Liebert Series 600T. Liebert Series 600T User Manual Instrukcja obsługi

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 128
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów

Podsumowanie treści

Strona 1 - Series 600T™ UPS

POWER PROTECTIONSeries 600T™ UPSMulti-Module Three Phase65 kVA to 750 kVA; 60 HzOperation & MaintenanceManual

Strona 2

4Introduction(retransferred) to the UPS. How and when the load is returned to the UPS depends on several factors: how longthe overload lasted, how man

Strona 3 - TABLE OF CONTENTS

94 OperationUPS Module Start-UpWhen a UPS module has been shut down for any reason, use this procedure to start-up the UPS module to pro-vide filtered

Strona 4

Operation 95Figure 60 Module Start-Up Procedures ScreenSelect the Walk-In screen on the LCD display.Step 3. To energize the UPS module, manually close

Strona 5

96 OperationThe Battery block in the Monitor/Mimic Display indicates the battery voltage and charge current.Use the Monitor/Mimic Display screen to de

Strona 6

Operation 973.3.2 Load Transfer ProceduresUse the Monitor/Mimic Display at the SCC to determine the operating condition of the UPS system. Press theAl

Strona 7 - IMPORTANT SAFETY INSTRUCTIONS

98 OperationMaintenance Bypass Load TransfersTo manually transfer the load between Maintenance Bypass and the UPS system bypass line, carefully follow

Strona 8 - OVERVIEW OF THIS MANUAL

Operation 993.3.3 Shutdown ProceduresSystem Shutdown ProcedurePerform a System Shutdown Procedure when you want to remove power from the UPS system an

Strona 9 - 1.0 INTRODUCTION

100 OperationStep 3. If maintenance is required in the area of the SCC controls or the motorized system circuit breakers (UPSOutput and SBB), transfer

Strona 10 - 4Introduction

Operation 101Module Shutdown ProcedurePerform a Module Shutdown Procedure when you want to remove power from a UPS module when required formaintenance

Strona 11 - Introduction 5

102 OperationStep 3. Manually open the UPS input circuit breaker by moving the handle to the OFF position (Figure 8).Return to the Monitor/Mimic Displ

Strona 12 - 6Introduction

Operation 1033.4 Automatic OperationsThe Liebert Series 600T UPS system is designed to function while unattended by an operator. The system con-trol l

Strona 13 - 1.2 Reliability

Introduction 5Figure 2 Multi-Module 500-750 kVA UPS

Strona 14 - 1.3 Safety Precautions

104 Operation3.4.2 Automatic Transfers to BypassThe UPS system will initiate an automatic load transfer to the bypass line if an overload condition ex

Strona 15 - 1.4 Modes of Operation

Operation 1053.4.4 Automatic Module Off-LineFor specified UPS module faults, the control logic will initiate an automatic isolation and shutdown of th

Strona 16 - 1.5 Operator Controls

106 Maintenance4.0 MAINTENANCEIf you require assistance for any reason, call the toll-free Liebert Global Services number: 1-800-543-2378. ForLGS to a

Strona 17 - Introduction 11

Maintenance 107WARNINGEXTREME CAUTION IS REQUIRED WHEN PERFORMINGMAINTENANCE.BE CONSTANTLY AWARE THAT THE UPS SYSTEM CONTAINS HIGHDC AS WELL AS AC VOL

Strona 18 - 1.6 Options

108 Maintenance4.2 Liebert Global ServicesStart-up, UPS maintenance, battery maintenance, and training programs are available for the Series 600T UPSt

Strona 19 - 2.0 THEORY OF OPERATION

Maintenance 1094.3 Routine MaintenanceYou are encouraged to become thoroughly familiar with the equipment, but at no time should you go beyond thespec

Strona 20 - Battery Plant

110 Maintenance4.3.3 Battery MaintenanceBattery Safety PrecautionsServicing of batteries should be performed or supervised by personnel knowledgeable

Strona 21 - Operation

Maintenance 111Battery Safety Precautions In French Per CSA RequirementsInstructions Importantes Concernant La SecuritéConserver Ces InstructionsADVER

Strona 22 - 16 Theory of Operation

112 MaintenanceDANGERL’électrolyte est un acide sulfurique dilué qui est dangereux au contact de lapeau et des yeux. Ce produit est corrosif et aussi

Strona 23 - Battery Disconnect

Maintenance 113Regular maintenance of the battery module is an absolute necessity. Periodic inspections of battery and terminalvoltages, specific grav

Strona 24 - 2.2.4 Inverter

6IntroductionFigure 3 System Control Cabinets (SCCs)Types of System Control Cabinets (SCCs)• SCCT -- A stand-alone cabinet containing system control l

Strona 25 - Static Switch Isolation

114 MaintenanceMatching Battery Cabinets (Optional)Although the individual battery cells are sealed (valve-regulated) and require only minimal mainten

Strona 26 - Load Transfers

Maintenance 1154.4 Detection of TroubleThere is no practical way to anticipate an impending malfunction. It is important that the operator check thein

Strona 27 - Theory of Operation 21

116 Maintenance4.5 Reporting a ProblemIf a problem occurs within the UPS, review all alarm messages along with other pertinent data. This informations

Strona 28 - 2.2.6 Redundant Mode

Specifications and Ratings 1175.0 SPECIFICATIONS AND RATINGS5.1 RatingThe kVA and kW ratings and the nominal voltages and currents for continuous oper

Strona 29 - 3.0 OPERATION

118 Specifications and Ratings5.2 Environmental ConditionsEnclosure: The UPS is housed in a NEMA-1 enclosure. The enclosure isdesigned for indoor use

Strona 30

Specifications and Ratings 1195.3 AdjustmentsAll adjustments are set at the factory or during start-up and normally do not have to be field readjusted

Strona 31

120 Specifications and Ratings5.5 Electrical SpecificationsRECTIFIER INPUTInput Voltage: Standard voltages—208 VAC, 480 VAC, 600 VAC. Other voltages a

Strona 32

Specifications and Ratings 121CRITICAL LOAD OUTPUTOutput Voltage: Standard voltages—208Y/120 VAC, 480Y/277 VAC, 600Y/346 VAC. Othervoltages available

Strona 33

Revised: February 1999Series 600T™ UPSMulti-Module Three Phase65 kVA to 750 kVA; 60 HzTechnical SupportThe Company Behind The ProductsWith more than 5

Strona 34 - 28 Operation

Introduction 71.2 ReliabilityReliability is the most important design goal for Uninterruptible Power Systems. Liebert Series 600 UPS systemshave demon

Strona 35 - 3.1.1 Master Menu Screen

8Introduction1.3 Safety PrecautionsRead this manual thoroughly, paying special attention to the sections that apply to you, before working with theUPS

Strona 36 - 30 Operation

Introduction 91.4 Modes of OperationRefer to 2.0 - Theory of Operation and 3.0 - Operation for more details.1.4.1 Normal (Load on UPS)The utility AC s

Strona 37 - Output Metering Displays

10 Introduction1.5 Operator ControlsThe Liebert Series 600T UPS System Control Cabinet (SCC) and each individual module are equipped with amicroproces

Strona 38 - Status/Alarm Message Areas

Introduction 11Figure 5 Module Controls and Display Screen with Example of the Monitor/Mimic Screen

Strona 39

12 Introduction1.6 OptionsA number of standard pre-designed options are available from Liebert for your UPS system. Described below arethe most freque

Strona 40 - Alarm Messages

Theory of Operation 132.0 THEORY OF OPERATION2.1 General Component DescriptionsThe UPS system includes all of the equipment necessary to continuously

Strona 42 - 36 Operation

14 Theory of OperationFigure 6 UPS Module Block DiagramUPS ModuleThe UPS module consists of module controls, a rectifier/charger, an inverter, protect

Strona 43 - Operation 37

Theory of Operation 152.2 Detailed Component Descriptions2.2.1 ControlsHardwareThe Series 600T UPS Operator Interface Display System is designed to pr

Strona 44 - SCC (above) and Module

16 Theory of Operationfull load with optional input filter. For modules 500 kVA and larger, the optional 12-pulse rectifier reducesreflected THD to le

Strona 45 - Operation 39

Theory of Operation 17Operation After End-of-DischargeThe battery time screen displayed on the control panel enables you to estimate when battery shut

Strona 46 - 3.1.3 Walk-In Display Screen

18 Theory of Operation2.2.4 InverterThe inverter is a solid state device that converts the DC output of the rectifier/charger or the battery to AC pow

Strona 47 - 3.1.4 Status Reports Screens

Theory of Operation 192.2.5 Static BypassA static bypass is an integral part of the UPS System Control Cabinet (SCC). Refer to Figure 7.Thestaticbypas

Strona 48 - Present Status

20 Theory of OperationAlso, if required for maintenance, the static switch can be isolated from the bypass line by opening (to the OFFposition) the St

Strona 49 - Event History

Theory of Operation 21Transfer and Retransfer Conditions1. Automatic Transfers to BypassCritical bus conditions that will initiate an automatic transf

Strona 50 - History Status

22 Theory of Operation5. Manual RetransfersManual retransfers may be initiated at any time provided no retransfer inhibition conditions are present.6.

Strona 51

Operation 233.0 OPERATION3.1 Display Screen and Operator ControlsEach Liebert Series 600T UPS cabinet is equipped with a microprocessor-based Operator

Strona 52 - System Status

iTABLE OF CONTENTS1.0 INTRODUCTION1.1 System Description . . . ...31.2 Reliability . ...

Strona 53 - Operation 47

24 OperationFigure 8 Operator Controls, 65 to 80 kVA (left) and 100 to 500 kVA (right)Item Description Function1 Input Circuit Breaker(behind door of

Strona 54 - 48 Operation

Operation 25Figure 9 System Control Cabinet Operator Controls (SCCB Pictured)Item Description Function1UPSOutputCircuitBreakerThis motorized circuit b

Strona 55 - Operation 49

26 OperationFigure 10 Series 600T UPS and SCC Operator Control PanelsItem Description (Location) Function1 Display Screen(SCC and modules)This screen

Strona 56 - 50 Operation

Operation 27Figure 11 Switches Behind SCC Control Panel DoorItem Description (Location) Function1 Interlock Button(on rear of Control Panel)Press this

Strona 57 - Auto Dial

28 OperationFigure 12 Menu TreeFigure 12 illustrates the primary screens that you can access through the Operator Interface Display System. Theliquid

Strona 58 - Modem Baud Rate

Operation 293.1.1 Master Menu ScreenThe Master Menu contains the primary menu selections that monitor and control the operation of the UPS.Figure 13 M

Strona 59 - Operation 53

30 Operation3. STATUS REPORTS.This display consists of three sub-menu selections: present status, history status, and event history. Thesescreens disp

Strona 60 - Remote Monitor

Operation 313.1.2 Monitor/Mimic Display ScreenFrom SCC Master Menu move the highlighted cursor to MONITOR/MIMIC DISPLAY. Press the Select padand the M

Strona 61 - Operation 55

32 OperationStatus/Alarm Message AreasThe status/alarm message areas display vital information about the operation of the UPS system. During normalope

Strona 62 - 56 Operation

Operation 33From module Master Menu move the highlighted cursor to MONITOR/MIMIC DISPLAY. Press the Selectpad and the Monitor/Mimic screen is displaye

Strona 63 - Operation 57

ii3.2.3 MomentaryOverloads...813.2.4 InputPowerFailure(LoadOnBattery)...

Strona 64 - SELECT :

34 OperationAlarm MessagesThe alarm message area displays vital information about the operation of the UPS system. During normal opera-tion no alarm m

Strona 65 - Operation 59

Operation 35Figure 16 through Figure 20 illustrate how the Monitor/Mimic Display screens on the SCC and on a moduledepict the power flow through the U

Strona 66 - SHUTDOWN PROCEDURES

36 OperationFigure 17 Monitor/Mimic Display Screen Examples: Utility Fail, SCC (above) and ModuleUPS RATINGSLOADByp Not AvailStatic Sw UnableModule Su

Strona 67 - Operation 61

Operation 37Figure 18 Monitor/Mimic Display Screen Examples: Load on Bypass, UPS Modules On and ChargingBattery, SCC (above) and ModuleUPS INPUT PWRUP

Strona 68 - 62 Operation

38 OperationFigure 19 Monitor/Mimic Display Screen Examples: Load on UPS, One UPS Module Off LineSCC (above) and ModuleUPS INPUT PWRBATTERYVOLTS 540AM

Strona 69 - Operation 63

Operation 39Figure 20 Monitor/Mimic Display Screen Examples: Load on Bypass, All UPS Modules Off LineUPS INPUT PWRBATTERYVOLTS 540AMPS 75 CHARGUPS RAT

Strona 70 - Calculated Time Remaining

40 Operation3.1.3 Walk-In Display ScreenFrom the module Master Menu, highlight WALK-IN DISPLAY and then press the Select pad. Note that thisscreen is

Strona 71 - Operation 65

Operation 413.1.4 Status Reports ScreensGo to the Master Menu and move the highlighted cursor to STATUS REPORTS. Press the Select button and theStatus

Strona 72 - 66 Operation

42 OperationPresent StatusThe Present Status screen shows the current status of the UPS system (SCC) or module. This screen displays anyalarm messages

Strona 73 - Module Status Messages

Operation 43Event HistoryThe Event History screen lists the active alarms present in the UPS system (SCC) or modules. This screen alsodisplays the pri

Strona 74 - Load Block Messages

iiiFIGURESFigure 1 Multi-Module UPS, 65-80 kVA (left) and 100-500 kVA (right) ...3Figure 2 Multi-Module 500-750 kVA UP

Strona 75

44 OperationHistory StatusThe History Status screen displays 64 frames, of 4 milliseconds each, from the Present Status screen. Note thatthe values fo

Strona 76

Operation 45The alarm conditions that cause the History Status buffer to stop gathering new data are:Note that the Emergency Off alarm will also freez

Strona 77

46 OperationSystem StatusThe System Status screen displays the module Total Operating Hours and the Battery Cycle Monitor.Battery Cycle Monitor (Modul

Strona 78

Operation 47Active Cycle Time in place of Accumulated Battery Time, and shows Active Battery AH and Active BatterykWH instead of accumulated values.Fi

Strona 79

48 Operation3.1.5 System Configuration ScreensGo to the Master Menu and move the highlighted cursor to SYSTEM CONFIGURATION. Press the Select padand t

Strona 80

Operation 49DateThis is the system’s real-time date setting. The system control program sends to each module the date entered atthe System Control Cab

Strona 81 - Worldwide Reporting

50 OperationTimeThis is the system’s real-time clock. The system control program sends to each module the time entered at theSystem Control Cabinet (S

Strona 82 - Remote Monitor Panel

Operation 51Auto DialThis is a feature that automatically dials (through a customer supplied PC-compatible modem) a pre-pro-grammed telephone number (

Strona 83

52 OperationModem Baud RateThis sets the transmission rate at which the system relays data to a terminal through the modem.Figure 33 Modem Baud RateTo

Strona 84 - 3.2 Modes of Operation

Operation 53Maximum Auto-Retransfer AttemptsWhen a UPS output overload condition exceeds a pre-programmed current-versus-time window (based on theSCC

Strona 85 - 3.2.2 OK To Transfer

ivFigure50 MomentaryOverload(PulsedStaticBypassSwitch)...81Figure51 InputPowerFail(LoadonBattery) ...

Strona 86

54 OperationRemote MonitorThe Remote Monitor Panel (optional) displays eight (8) alarms. These alarms are also available for customer usethrough a set

Strona 87 - 3.2.3 Momentary Overloads

Operation 553.1.6 Alarm Limit Settings ScreenGo to the Master Menu and move the highlighted cursor to LIMIT SETTINGS. Press the Select pad and theLimi

Strona 88

56 OperationBattery Rating (modules only). This setting is a battery discharge rating in kilowatts under partial load for anextended period, typically

Strona 89 - 3.2.5 One Module Off-Line

Operation 573.1.7 Load Transfer Procedures ScreenGo to the SCC Master Menu and move the highlighted cursor to LOAD TRANSFER PROCEDURES. Notethat this

Strona 90 - 3.2.6 Off Battery

58 Operation3.1.8 Start-Up Procedures ScreenFrom the SCC Master Menu, move the highlighted cursor to START-UP PROCEDURES. Press the Select padand the

Strona 91 - 3.2.7 Emergency Modules Off

Operation 59From the module Master Menu, move the highlighted cursor to START-UP PROCEDURES. Press the Selectpad and the module Start-Up Procedures sc

Strona 92 - 3.2.8 Emergency Power Off

60 Operation3.1.9 Shutdown Procedures ScreenGo to the SCC Master Menu and move the cursor to SHUTDOWN PROCEDURES. Press the Select pad andthe SCC Shut

Strona 93 - 3.2.9 System Shutdown

Operation 61Go to the module Master Menu and move the cursor to SHUTDOWN PROCEDURES. Press the Select padand the module Shutdown Procedures screen is

Strona 94 - 3.2.10 Maintenance Bypass

62 Operation3.1.10 Battery Time Screen (Module Only)At the Master Menu, move the highlighted cursor to BATTERY TIME. Press the Select pad and the Batt

Strona 95 - TRANSFER SWITCH

Operation 63Figure 42 Battery Time Screen Example - 45 Minute DischargeThe Battery Time Remaining graph and the Calculated times are extremely helpful

Strona 96 - 3.3 Manual Procedures

1IMPORTANT SAFETY INSTRUCTIONSSave These Instructions.This manual contains important instructions that should be followed during installation and main

Strona 97 - SCC Start-Up

64 OperationFigure 43 Range of Values for Calculated Battery TimesIf the Battery Time screen is displayed while the battery is not discharging, it wil

Strona 98 - 92 Operation

Operation 653.1.11 Meter Calibration ScreenGo to the Master Menu and move the highlighted cursor to METER CALIBRATION. Press the Select pad andthe Met

Strona 99 - MASTER MENUSELECT :

66 Operation3.1.12 Battery Equalize ScreenGo to the Master Menu and move the highlighted cursor to BATTERY EQUALIZE. Press the Select pad andthe Batte

Strona 100 - UPS Module Start-Up

Operation 673.1.13 Alarm and Status MessagesModule Status MessagesThe module status messages indicate how many UPS modules are included in the system

Strona 101 - Operation 95

68 OperationSystem Status MessagesThe system status messages indicate whether the static bypass switch is connected or disconnected, through themanual

Strona 102 - 96 Operation

Operation 69Alarm MessagesThe alarm message area displays the alarm conditions that are present within the UPS system. Alarm messagesare displayed in

Strona 103 - Operation 97

70 OperationTable 1 Alarm Messages - Meaning and Corrective ActionAlarmMessageCabinetLocationSpecialFunctionsMeaning andCorrective Action in Brackets

Strona 104 - 98 Operation

Operation 71BYPASS (Cont’d.)Auto Transfer toBypassSCC D, E, F The critical load has been automatically transferred to the bypassline.[Use the History

Strona 105 - System Shutdown Procedure

72 OperationUPS SYSTEM (Cont’d.)Overload SCCMMUR, SSThe UPS output current exceeds the rated system load current. Thiscondition causes an alarm only,

Strona 106 - 100 Operation

Operation 73UPS SYSTEM (Cont’d.)HardwareShutdownMMU D# At least one of the following alarm conditions is present: InverterFault, Rectifier Fuse Blown,

Strona 107 - Module Shutdown Procedure

2OVERVIEW OF THIS MANUALThe manual is organized so that information can be found quickly. Each major topic is separated by sections, andthe Table of C

Strona 108 - 102 Operation

74 OperationTable 2 Alarm Messages - SummaryAlarm Message MMU SCC Special FunctionsInput Fail X — —DC Ground Fault X — L, SDC Capacitor Fuse Blown X —

Strona 109 - 3.4 Automatic Operations

Operation 753.1.14 Communication InterfacesYour Liebert Series 600T UPS includes the following communication ports:• Worldwide reporting to a remote t

Strona 110 - 104 Operation

76 Operationmands) and then the Enter key. The Series 600T will send the data, which will be displayed on your screen. Tosee the Present Status Report

Strona 111 - Operation 105

Operation 77Separate / Simultaneous OutputsThe RS-232 interface can support a modem plus either a local terminal or a local monitor. Likewise, the Sit

Strona 112 - 4.0 MAINTENANCE

78 Operation3.2 Modes of OperationThis section illustrates the flow of power through circuit breakers, switches, and UPS components during variousmode

Strona 113 - Maintenance 107

Operation 793.2.2 OK To TransferThe OK to Transfer status message will be displayed when the bypass line and UPS system output power areboth available

Strona 114 - 4.2 Liebert Global Services

80 OperationFigure 49 Load on UPS (Bypass Available)BIBSKRUMIBMBBIR#2UPSCB1CB2IR#1UPSCB1SystemControlsIR#3UPSCB1CB2RIB RIBCB2RIB BFBOutputSBBSBSSCCTSC

Strona 115 - 4.3 Routine Maintenance

Operation 813.2.3 Momentary OverloadsAn overload in the critical load will continue to be supplied by the UPS system if the overload condition does no

Strona 116 - Battery Safety Precautions

82 Operation3.2.4 Input Power Failure (Load On Battery)If the utility AC power source fails, or is outside the acceptable range, the battery plant bec

Strona 117 - Conserver Ces Instructions

Operation 833.2.5 One Module Off-LineA multi-module UPS system can be supplied with a back-up (redundant) UPS module, which is the typical con-figurat

Strona 118 - 112 Maintenance

Introduction 31.0 INTRODUCTION1.1 System DescriptionThe role of the parallel-redundant multi-module UPS system is to supply uninterruptible, clean pow

Strona 119

84 Operation3.2.6 Off BatteryThe battery plant can be disconnected from the UPS modules, if required for battery maintenance, by opening themodule bat

Strona 120 - 4.3.4 Torque Requirements

Operation 853.2.7 Emergency Modules OffThe Local Emergency Modules Off (LEMO) mode is used to remove power from all UPS system components,and the crit

Strona 121 - 4.4 Detection of Trouble

86 Operation3.2.8 Emergency Power OffThe Remote Emergency Power Off (REPO) mode is used to remove all power from the critical load.The Remote Emergenc

Strona 122 - 4.6 Corrective Actions

Operation 873.2.9 System ShutdownPerform a System Shutdown procedure when you must disconnect the UPS system components from all powersources when req

Strona 123 - 5.1 Rating

88 Operation3.2.10 Maintenance BypassMaintenance Bypass switchgear (cabinet, panelboard, switchboard or custom switchgear) allows you to totallyisolat

Strona 124 - 5.2 Environmental Conditions

Operation 89Figure 58 Load on Maintenance Bypass (Three Breakers)IRCB2SystemControlsBFBOutputSBBSBSBIBIRIRCB2 CB2#2UPSCB1#1UPSCB1#3UPSCB1RIB RIBRIBTo

Strona 125 - 5.4 Battery Operation

90 Operation3.3 Manual ProceduresThe Liebert Series 600T UPS system is designed to function while unattended by an operator. The system con-trol logic

Strona 126 - 5.5 Electrical Specifications

Operation 913.3.1 Start-Up ProcedureSCC Start-UpWhen the UPS system has been shut down, for any reason, use this procedure to start-up the UPS system

Strona 127

92 OperationPower must be provided to the UPS controls so the operator can use the LCD display and so the system logic canperform its control function

Strona 128 - Technical Support

Operation 93b3. Find the Close Bypass switch (SW1) on the System Interface Board (Figure 11). Press this switchto reset the System Bypass circuit brea

Komentarze do niniejszej Instrukcji

Brak uwag