POWER PROTECTION Series 600T™ UPSSingle Module Three Phase500 kVA to 750 kVA, 60 HzInstallationManual

Strona 2

4 Installation Considerations2.0 INSTALLATION CONSIDERATIONSInstall your Series 600T UPS in accordance with the submittal drawing package and

Strona 3 - Table of Contents

Unloading and Handling 53.0 UNLOADING AND HANDLINGThe UPS module is shipped in one cabinet to allow easy handling at the site. Because the we

Strona 4

6 Inspections4.0 INSPECTIONS4.1 External Inspections1. While the UPS system is still on the truck, inspect the equipment and shipping contain

Strona 5 - List of Figures

Equipment Location 75.0 EQUIPMENT LOCATION1. Handle cabinet(s) in accordance with WARNINGS in 16.0 - Unloading and Handling. Use a suitable m

Strona 6

8 Battery Installation6.0 BATTERY INSTALLATION6.1 Battery Safety PrecautionsServicing of batteries should be performed or supervised by perso

Strona 7 - IMPORTANT SAFETY INSTRUCTIONS

Battery Installation 9Battery Safety Precautions in French Per CSA RequirementsInstructions Importantes Concernant La SécuritéConserver Ces I

Strona 8

10 Battery InstallationLes accumulateurs plomb-acide présentent un risque d’incendie parce qu’ils génèrent des gaz à l’hydrogène. Les procédu

Strona 9 - 1.0 SAFETY PRECAUTIONS

Battery Installation 116.2 Battery CabinetsTwo sizes of optional battery cabinets are available. Refer to Figure 11 through Figure 13. The ba

Strona 10 - NSTALLATION CONSIDERATIONS

12 Configuring Your Ground and Neutral Connections7.0 CONFIGURING YOUR GROUND AND NEUTRAL CONNECTIONSImproper grounding is the largest single

Strona 11 - 3.0 UNLOADING AND HANDLING

Configuring Your Ground and Neutral Connections 137.1 Preferred Grounding Configuration, 480 or 600 VAC Input and Output, Isolated Power Dist

Strona 13 - 5.0 EQUIPMENT LOCATION

14 Configuring Your Ground and Neutral Connections7.2 Alternative Grounding Configuration, 480 or 600 VAC Input and Output, Isolated Power Di

Strona 14 - 6.0 BATTERY INSTALLATION

Configuring Your Ground and Neutral Connections 157.3 Grounding Configuration, 480 or 600 VAC Input and Output, Delta Source or Impedance-Gro

Strona 15 - Conserver Ces Instructions

16 Configuring Your Ground and Neutral Connections7.4 Preferred Grounding Configuration, 480 or 600 VAC Input and Output, with Power-Tie™ Swi

Strona 16

Configuring Your Ground and Neutral Connections 177.5 Preferred Grounding Configuration, Battery Systems Figure 5 Preferred Battery Cabinet G

Strona 17 - 6.3 Non-Standard Batteries

18 Wiring Considerations8.0 WIRING CONSIDERATIONS Refer to Appendix A - Site Planning Data and installation drawings in Figure 7 through Figu

Strona 18

Wiring Considerations 198.1 Power and Control Wiring1. Power wiring must be run in individual, separate conduit or cable tray. Control wiring

Strona 19 - PER NEC 250-24

20 Wiring ConsiderationsFigure 6 Typical Power Wiring Abbreviations for Circuit BreakersBFB Bypass Feeder BreakerBIB Bypass Input BreakerMBB

Strona 20

Wiring Connections 219.0 WIRING CONNECTIONS Refer to the drawings in this manual and any other drawings provided by Liebert for this installa

Strona 21 - Impedance-Grounded Wye

22 Wiring Connections4. The UPS Module Output Neutral is connected to one common point and solidly grounded per requirements of the National

Strona 22 - Power-Tie™ Switchgear

Wiring Inspection 2310.0 WIRING INSPECTION1. Verify all power connections are tight.2. Verify all control wire terminations are tight.3. Veri

Strona 23 - DISTRIBUTIO

Table of Contents1.0 SAFETY PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Strona 24 - 8.0 WIRING CONSIDERATIONS

24 Wiring InspectionTable 1 Power Wiring Terminals - Factory SuppliedUPS Module Rating kVAConnection Type500-750 kVA Bus bars for connecting

Strona 25 - 8.2 Battery Wiring

Wiring Inspection 25Table 3 Table 310-16Allowable Ampacities of Insulated Conductors Rated 0-2000 Volts, 60° to 90°C (140° to 194°F)1Not More

Strona 26

26 Installation Drawings11.0 INSTALLATION DRAWINGSFigure 7 Outline Drawing, 500 kVA Single Module UPS, 6-Pulse Rectifier

Strona 27 - 9.0 WIRING CONNECTIONS

Installation Drawings 27Figure 8 Outline Drawing, 500 kVA Single Module UPS, 12-Pulse Rectifier

Strona 28

28 Installation DrawingsFigure 9 Outline Drawing, 625-750 kVA Single Module UPS, 6-Pulse Rectifier

Strona 29 - 10.0 WIRING INSPECTION

Installation Drawings 29Figure 10 Outline Drawing, 625-750 kVA Single Module UPS, 12-Pulse Rectifier

Strona 30 - Table 2 Torque Specifications

30 Installation DrawingsFigure 11 Battery Cabinet, Size A

Strona 31 - Table 3 Table 310-16

Installation Drawings 31Figure 12 Battery Cabinet, Size B

Strona 32 - 11.0 INSTALLATION DRAWINGS

32 Installation DrawingsFigure 13 Parallel Battery Power Pack

Strona 33

Installation Drawings 33Figure 14 Base Mounting Patterns, 500 kVA SMS, 12-Pulse Rectifier

Strona 35

34 Installation DrawingsFigure 15 Base Mounting Patterns, 625-750 kVA SMS, 6-Pulse Rectifier

Strona 36

Installation Drawings 35Figure 16 Base Mounting Patterns, 625-750 kVA SMS, 12-Pulse Rectifier

Strona 37

36 Installation DrawingsFigure 17 Shipping Split Detail, 500 kVA SMS, 12-Pulse Rectifier

Strona 38

Installation Drawings 37Figure 18 Shipping Split Detail, 625-750 kVA SMS, 6-Pulse Rectifier

Strona 39

38 Installation DrawingsFigure 19 Shipping Split Detail, 625-750 kVA SMS, 12-Pulse Rectifier

Strona 40

Installation Drawings 39Figure 20 Bussing Details, 500 kVA SMS, 6-Pulse Rectifier

Strona 41

40 Installation DrawingsFigure 21 Bussing Details, 500 kVA SMS, 12-Pulse Rectifier

Strona 42

Installation Drawings 41Figure 22 Bussing Details, 625-750 SMS, 12-Pulse Rectifier

Strona 43

42 Installation DrawingsFigure 23 Bussing Details, 750 kVA/675 kW Standard and 750 kVA/600 kW Optional Input Busbars, SMS, 12-Pulse Rectifier

Strona 44

Installation Drawings 43Figure 24 Control Wiring, External Interconnect Diagram, SMS with Maintenance Bypass Panelboard or Switchboard

Strona 45

List of FiguresFigure 1 Preferred Grounding Configuration, 480 or 600 VAC input and output. . . . . . . . . . . . . . . . . 13Figure 2 Alternative Gr

Strona 46

44 Installation DrawingsFigure 25 Control Connection Location Diagram, 500 kVA SMS

Strona 47

Installation Drawings 45Figure 26 Control Connection Location Diagram, 625-750 kVA SMS

Strona 48 - SMS, 12-Pulse Rectifier

46 Installation DrawingsFigure 27 Control Wire List, External Interconnections, 500-750 kVA SMS

Strona 49

Installation Drawings 47Figure 28 Control Wiring, Alarm Status Contacts Option

Strona 50

48 Installation DrawingsFigure 29 Control Wiring, Maintenance Bypass Interlock Option

Strona 51

Installation Drawings 49Figure 30 Control Wiring, Remote Status Panel Interface Option

Strona 52

50 Installation DrawingsFigure 31 Control Wiring, Remote Terminal IFM (RS-232 Communications) Option

Strona 53

Installation Drawings 51Figure 32 Control Wiring, SiteScan Interface

Strona 54

52 Installation DrawingsFigure 33 Control Wiring, Customer Alarm Interface Option

Strona 55

Installation Drawings 53Figure 34 Control Wiring, Battery Temperature Sensor Interface

Strona 57

54 Installation DrawingsFigure 35 Control Wiring, SNMP Interface Option

Strona 58

Installation Drawings 55Figure 36 Control Wiring, Internal Modem Option

Strona 59

56 Installation DrawingsFigure 37 Control Wiring, Maintenance Bypass Cabinet Option

Strona 60

Installation Drawings 57Figure 38 Wiring Configurations, UPS Video Display Terminal

Strona 61

58 Installation DrawingsFigure 39 Outline Drawing, Module Battery Disconnect, 500 kVA SMS with 6-Pulse Rectifier

Strona 62

Installation Drawings 59Figure 40 Outline Drawing, Module Battery Disconnect, 500-750 kVA SMS with 12-Pulse Rectifier

Strona 63

60 Installation DrawingsFigure 41 Remote Status Panel, Surface Mount

Strona 64

Installation Drawings 61Figure 42 Circuit Breaker Schedule, 300-750 kVA

Strona 65

62 Appendix A - Site Planning Data12.0 APPENDIX A - SITE PLANNING DATA500-750 kVA Single Module Systems 12.1 Notes1. Nominal rectifier AC inp

Strona 66

Appendix A - Site Planning Data 63Table 4 Site Planning Data, 480 Volt InputUPS Rating ACOutput VoltageOptions Rectifier AC Input CurrentInve

Strona 67

1IMPORTANT SAFETY INSTRUCTIONSSave These Instructions.This manual contains important instructions that should be followed during installatio

Strona 68 - 12.1 Notes

64 Appendix A - Site Planning DataTable 5 Site Planning Data, 600 Volt InputTable 6 Circuit Breaker RatingsUPS Rating ACOutput VoltageOptions

Strona 69

Appendix B - Field Supplied Lugs 6513.0 APPENDIX B - FIELD SUPPLIED LUGSTable 7 One-Hole LugsT & B1 Lug StyleWire SizeBolt Size(Inches)To

Strona 70

66 Appendix B - Field Supplied Lugs

Strona 71 - Table 7 One-Hole Lugs

Revised: June 2000Series 600T™ UPSSingle Module Three Phase 500kVA to 750 kVA, 60 HzTechnical SupportThe Company Behind The ProductsWith more than 500

Strona 72

2 If you require assistance for any reason, call the toll-free Liebert Global Services number; 1-800-543-2378. For LGS to assist you expedien

Strona 73 - Technical Support

Safety Precautions 31.0 SAFETY PRECAUTIONSRead this manual thoroughly, paying special attention to the sections that apply to you, before wor